Motor full load current: converting kW to amps
How to turn a motor's kW rating into amps: the three-phase and single-phase formulas, why efficiency and power factor matter, starting current, and a worked 11 kW, 400 V example.
Every motor nameplate gives a power in kW (or hp), but the cable, the breaker, the overload relay, the starter and the generator are all chosen on current. Getting from kW to amps is a one-line formula, as long as you remember the two numbers people most often leave out: the motor's efficiency and its power factor. This guide shows the formula for three-phase and single-phase motors, how starting current compares with running current, and a full worked example for an 11 kW motor on a 400 V supply.
Why the kW on the nameplate is not the power you pay for
The rated power of an induction motor is the mechanical output at the shaft, not the electrical power it takes from the supply. Two things sit between the two:
- Efficiency (η): some of the electrical input is lost as heat in the windings, the iron core, the bearings and the cooling fan. A modern 11 kW, 4-pole IE3 motor is around 91% efficient at full load, so it takes about 12 kW of real power to deliver 11 kW at the shaft.
- Power factor (cos φ): an induction motor also draws reactive current to magnetise its core. That current does no useful work, but it flows through the cable and the switchgear just the same. A typical full-load power factor for mid-size motors is about 0.80 to 0.88, and it falls sharply at light load.
So the supply has to deliver more apparent power (kVA) than the shaft delivers in kW, and current follows the kVA, not the kW.
Motor full load current formula
Three-phase motors
I = P × 1000 / (√3 × V × η × cos φ)
- I = line current, A
- P = rated (shaft) power, kW
- V = line-to-line voltage, V (for example 400 V, 415 V or 380 V)
- η = efficiency at the load considered, as a decimal
- cos φ = power factor at the load considered
- √3 ≈ 1.732
The same quantities give the electrical input power and the apparent power:
Pin (kW) = P / η and S (kVA) = √3 × V × I / 1000 = P / (η × cos φ)
Single-phase motors
I = P × 1000 / (V × η × cos φ)
with V the phase voltage, for example 230 V. Small single-phase motors are less efficient than three-phase motors, so do not borrow three-phase figures. A 2.2 kW single-phase motor at 230 V with η = 0.78 and cos φ = 0.92 draws 2,200 / (230 × 0.78 × 0.92) = 13.3 A.
Horsepower and North American voltages
Convert horsepower with 1 hp = 746 W: I = hp × 746 / (√3 × V × η × cos φ). A 15 hp motor at 460 V with η = 0.92 and cos φ = 0.85 draws about 18.0 A. Note that the US National Electrical Code (NEC) tells you to size motor conductors and short-circuit protection from its own full-load current tables rather than the nameplate; for 15 hp at 460 V the table value is 21 A, deliberately higher than a modern motor's nameplate. The nameplate current is used for setting the overload protection.
The mistake that undersizes cables
The most common error is to drop η and cos φ and write I = P / (√3 × V). For an 11 kW motor at 400 V that gives 15.9 A, about 23% below the real full-load current of roughly 20.7 A. A cable, breaker or overload chosen on 15.9 A will run hot or trip. A useful sanity check: mid-size three-phase motors at 400 V draw roughly 1.8 to 2 A per kW at full load, and small motors (below about 2 kW) draw noticeably more per kW because their efficiency and power factor are lower. Unit slips such as kW and hp, or line and phase voltage, cause the same kind of error; our guide to converting engineering units without mistakes lists the usual traps, and the unit converter handles kW to hp and back.
Worked example: an 11 kW motor on 400 V
A centrifugal pump is driven by an 11 kW, 4-pole, IE3 motor on a 400 V, 50 Hz three-phase supply. From the motor datasheet: full-load efficiency η = 91.4% and power factor cos φ = 0.84. The motor is about 50 m from the distribution board.
Step 1: full-load current
I = 11 × 1000 / (1.732 × 400 × 0.914 × 0.84) = 11,000 / 531.9 = 20.7 A
Step 2: input power and apparent power
- Electrical input: Pin = 11 / 0.914 = 12.04 kW (losses 1.04 kW)
- Apparent power: S = 1.732 × 400 × 20.7 / 1000 = 14.3 kVA
- Reactive power: Q = √(14.3² − 12.04²) ≈ 7.8 kvar
Step 3: the same motor on other voltages
For the same power, current is inversely proportional to voltage: at 415 V the motor draws about 19.9 A and at 380 V about 21.8 A. This is why a motor nameplate usually lists more than one voltage and current. Always use the current for the voltage you actually have.
Step 4: starting current
Started direct on line (DOL), an induction motor typically draws 6 to 8 times its full-load current for a few seconds; the exact figure is the locked-rotor current ratio (IA/IN) on the datasheet. With a ratio of 7, this motor pulls about 145 A at the instant of starting. A star-delta starter cuts the starting current, and the starting torque, to one third of the DOL value, here about 48 A. A soft starter is usually set to around 3 to 4 times full-load current (about 72 A at 3.5×), and a variable frequency drive (VFD) can start the motor at little more than full-load current. Starting current matters for the choice of starter, the breaker's trip curve, the voltage dip on weak supplies and, above all, generator sizing.
Step 5: a quick voltage drop check
For a balanced three-phase load, the voltage drop along a cable is approximately ΔV = √3 × I × L × (R cos φ + X sin φ), with L in km and R and X in Ω/km. For 50 m of 4 mm² copper cable (R ≈ 5.5 Ω/km at 70 °C, reactance negligible at this size), ΔV ≈ 1.732 × 20.7 × 0.05 × 5.5 × 0.84 = 8.3 V, about 2.1% of 400 V. That is inside common limits for motor circuits, but the cable size itself must come from the current-carrying tables in your local wiring standard (IEC 60364, BS 7671, NEC or similar), with derating for grouping, ambient temperature and installation method. The voltage drop during a DOL start is several times larger, which is worth checking on long runs.
Running current is not always full-load current
A motor draws its nameplate current only when it delivers its rated power. Pumps, fans and conveyors are often sized with a margin, so the motor runs at 60 to 90% load. At part load the current falls, but not in proportion, because the magnetising current stays almost constant while the power factor drops. A motor at half load typically still draws well over half of its full-load current.
The reverse calculation is useful in the field. If a clamp meter reads 17.2 A per phase on the 11 kW motor above and a power analyser shows cos φ = 0.80, the input power is Pin = 1.732 × 400 × 17.2 × 0.80 / 1000 = 9.5 kW, so the shaft delivers roughly 9.5 × 0.91 ≈ 8.7 kW. Without a measured power factor, current alone over-estimates the load on a lightly loaded motor. To find the power a pump really needs from its flow and head, see pump power and motor size from flow and head or the pump power calculator.
Typical full-load current at 400 V
The table gives planning values for 4-pole IE3 motors on 400 V, 50 Hz, using the IE3 minimum efficiencies of IEC 60034-30-1 and typical full-load power factors. Real motors vary by manufacturer and frame, so use the nameplate or datasheet for final selection.
Power (kW) | Efficiency η | Power factor | Full-load current (A) |
|---|---|---|---|
1.1 | 84.1% | 0.78 | 2.4 |
2.2 | 86.7% | 0.80 | 4.6 |
4 | 88.6% | 0.81 | 8.0 |
5.5 | 89.6% | 0.82 | 10.8 |
7.5 | 90.4% | 0.83 | 14.4 |
11 | 91.4% | 0.84 | 20.7 |
15 | 92.1% | 0.84 | 28.0 |
22 | 93.0% | 0.85 | 40.2 |
30 | 93.6% | 0.86 | 53.8 |
45 | 94.2% | 0.86 | 80.2 |
55 | 94.6% | 0.87 | 96.5 |
75 | 95.0% | 0.87 | 131.0 |
From current to the rest of the motor circuit
- Overload relay: set to the nameplate full-load current at the actual supply voltage (in a star-delta starter with the relay in the motor phase windings, set it to 0.58 × full-load current).
- Contactor: choose for the motor kW at the supply voltage in utilisation category AC-3, which already allows for the starting current.
- Circuit breaker or fuses: rated above full-load current with a characteristic (motor-protection breaker, or aM fuses) that rides through the starting current.
- Generator: size on kVA, not kW, and on the largest motor's starting kVA; a generator that runs the 14.3 kVA of this motor comfortably may still struggle with a DOL start that briefly demands about 100 kVA.
If you are still choosing the motor itself, start from the load: the motor and gearbox calculator works out power, torque and ratio, and our guide to choosing a motor and gearbox from power and speed explains service factors.
Quick reference
Quantity | Formula |
|---|---|
Three-phase current | I = P × 1000 / (√3 × V × η × cos φ) |
Single-phase current | I = P × 1000 / (V × η × cos φ) |
Current from hp | I = hp × 746 / (√3 × V × η × cos φ) |
Electrical input power | Pin = P / η = √3 × V × I × cos φ / 1000 kW |
Apparent power | S = √3 × V × I / 1000 kVA |
DOL starting current | ≈ 6 to 8 × I (datasheet IA/IN) |
Star-delta starting current | ≈ 1/3 of DOL |
Voltage drop | ΔV ≈ √3 × I × L × (R cos φ + X sin φ) |
The efficiencies and power factors used here are typical planning values. For the final design, take the full-load current, locked-rotor current ratio and power factor from the datasheet of the motor you are buying, and size cables and protection to your local electrical code.