Pump affinity laws: flow, head and power at a new speed

How flow, head and power change when you change a centrifugal pump's speed or trim its impeller, why static head breaks the simple cube law, and a worked example comparing a VFD with a throttling valve.

By Site AdministratorUpdated 7 min read

Slow a centrifugal pump down by 20% and its power drops by almost half. That single fact is why variable speed drives (VFDs) pay for themselves on so many pumps. It comes from the pump affinity laws, three short ratios that tell you how flow, head and power change when you change the speed or trim the impeller. This guide explains the laws, shows where they go wrong (systems with static head), and works through a full example: a 100 m³/h pump that needs to deliver 80 m³/h, comparing a throttling valve with a speed change.

The three affinity laws for speed

For the same pump with the same impeller, running at speed N₁ and then at N₂, the performance at equivalent points on the curve scales like this:

  • Flow: Q₂ / Q₁ = N₂ / N₁
  • Head: H₂ / H₁ = (N₂ / N₁)²
  • Power: P₂ / P₁ = (N₂ / N₁)³

Flow follows speed, head follows speed squared, and shaft power follows speed cubed. The ratios have no units, so they work in m³/h, L/s or US gpm, in metres or feet, and in kW or hp. Efficiency is assumed to stay the same at the equivalent point, which is a good approximation for moderate speed changes on a variable speed drive.

Pump curves at 1,450 and 1,250 rpm crossing a system curve with 15 m static head

What "equivalent point" means

The laws move every point of the pump curve together: the best efficiency point (BEP) at full speed moves to a new BEP at lower flow and lower head. They do not tell you where the pump will actually run in your plant. That depends on where the new pump curve crosses the system curve, and this is where most mistakes are made.

Affinity laws for impeller trimming

Trimming the impeller diameter D at constant speed gives similar ratios:

  • Q₂ / Q₁ ≈ D₂ / D₁
  • H₂ / H₁ ≈ (D₂ / D₁)²
  • P₂ / P₁ ≈ (D₂ / D₁)³

These are approximations. They are close for small trims of a few percent and become less reliable as more material is removed, because the impeller geometry no longer scales and efficiency falls. Trimming a 250 mm impeller to 237.5 mm (95%) predicts 95% of the flow, 90.25% of the head and about 85.7% of the power. Use the manufacturer's published curves for the trimmed diameter before you cut metal, and remember that a trim is permanent while a speed change is not.

When the simple laws give the wrong answer

The affinity laws predict the operating point directly only when the system curve is pure friction, H = k × Q², which passes through zero. Closed circulating loops (chilled water, heating, cooling circuits) come close to this. Most transfer, boosting and supply systems also have static head: the pump must lift the liquid to a higher level or push against a fixed pressure before any flow moves. Then the system curve is:

H_sys = H_static + k × Q²

With static head, cutting the speed by 20% does not cut the flow by 20%. The flow drops much faster, and below a certain speed the pump cannot overcome the static head at all and delivers nothing. To find the real operating point you have to scale the pump curve and intersect it with the system curve, as in the example below.

Worked example: 100 m³/h pump turned down to 80 m³/h

A water transfer pump runs at 1,450 rpm and delivers 100 m³/h at 40 m head with 75% efficiency. Its curve can be approximated by H = 52 − 0.0012 × Q² (Q in m³/h, H in m), so the shut-off head is 52 m. The system has 15 m of static head, and friction adds 25 m at 100 m³/h:

H_sys = 15 + 25 × (Q / 100)²

The process now needs only 80 m³/h for most of the year. What speed is needed, and how much power does it save compared with closing a valve?

Step 1: power at the design point

Hydraulic power P_h = ρ × g × Q × H = 1000 × 9.81 × (100 / 3600) × 40 = 10,900 W = 10.9 kW.

Shaft power P = 10.9 / 0.75 = 14.5 kW.

Step 2: the tempting (wrong) answer

Using the affinity law for flow alone: N₂ = 1,450 × 80 / 100 = 1,160 rpm, with predicted head 40 × 0.8² = 25.6 m and power 14.5 × 0.8³ = 7.4 kW. But the system needs 15 + 25 × 0.8² = 31 m at 80 m³/h, not 25.6 m. At 1,160 rpm the pump would fall short and deliver less than 80 m³/h.

Step 3: the correct speed

At speed ratio r = N₂ / N₁, the pump curve becomes H = 52 × r² − 0.0012 × Q². Setting it equal to the 31 m the system needs at 80 m³/h:

52 × r² = 31 + 0.0012 × 80² = 31 + 7.68 = 38.68, so r² = 0.744 and r = 0.862.

N₂ = 1,450 × 0.862 ≈ 1,250 rpm. This point corresponds to about 92.8 m³/h at full speed, close to the BEP, so keeping 75% efficiency is reasonable.

Shaft power: P_h = 9.81 × (80 / 3.6) × 31 / 1000 = 6.76 kW, so P = 6.76 / 0.75 = 9.0 kW.

Step 4: compare with throttling

With a valve at full speed, the pump runs on its 1,450 rpm curve at 80 m³/h: H = 52 − 7.68 = 44.3 m. The valve burns off 44.3 − 31 = 13.3 m. Further left on the curve the efficiency is lower; taking 72%:

P = 9.81 × (80 / 3.6) × 44.3 / 1000 / 0.72 = 9.66 / 0.72 = 13.4 kW.

Shaft power at 80 m3/h: 13.4 kW throttled, 9.0 kW with VFD, 7.4 kW cube-law estimate

Step 5: annual saving

Saving at the shaft: 13.4 − 9.0 = 4.4 kW. Over 6,000 operating hours a year that is about 26,500 kWh, or roughly 3,200 a year at a tariff of 0.12 per kWh. The VFD itself loses a few percent, so subtract that from the saving, but a payback of one to three years is typical on duties like this.

Step 6: minimum speed

At zero flow the pump produces 52 × r² of head. It can only lift the liquid while that exceeds the 15 m static head: r > √(15 / 52) = 0.537, or about 780 rpm. In practice, set the drive's minimum speed well above this, so the pump never runs dead-headed or far left of its BEP.

Results at a glance

Case
Speed (rpm)
Flow (m³/h)
Pump head (m)
Shaft power (kW)
Design point
1,450
100
40.0
14.5
Throttled with valve
1,450
80
44.3
13.4
VFD, correct speed
1,250
80
31.0
9.0
Cube law only (wrong)
1,160
80
25.6
7.4

The cube law alone would have promised 7.4 kW. The real figure with static head is 9.0 kW: still a large saving over throttling, but about 20% higher than the naive prediction. To check the motor and the drive at each speed, use the pump power calculator and the motor and drive calculator.

Practical checks before you change speed

  • Static head: the larger the share of static head, the less a speed reduction saves and the narrower the useful speed range.
  • NPSH: NPSH required falls roughly with speed squared when you slow down, and rises when you speed up. Running above rated speed can cause cavitation; see NPSH and cavitation.
  • Speeding up: 10% more speed needs about 33% more power (1.1³ = 1.33). Check the motor rating, the casing pressure rating and the manufacturer's maximum speed first.
  • Pipework: recheck velocity and friction losses at the new flow with the pipe flow calculator.
  • Motor cooling: a self-cooled motor driving a centrifugal pump is usually fine at reduced speed because the load torque falls with speed squared, but confirm the drive and motor are rated for the speed range.

For the basics of reading a pump curve, see how a centrifugal pump works and what its curve tells you, and for sizing the motor at the design point, pump power and motor size from flow and head.

Quick reference

Quantity
Speed change (same impeller)
Impeller trim (same speed)
Flow
Q₂ = Q₁ × (N₂ / N₁)
Q₂ ≈ Q₁ × (D₂ / D₁)
Head
H₂ = H₁ × (N₂ / N₁)²
H₂ ≈ H₁ × (D₂ / D₁)²
Power
P₂ = P₁ × (N₂ / N₁)³
P₂ ≈ P₁ × (D₂ / D₁)³
Hydraulic power
P_h (kW) = ρ × g × Q (m³/s) × H (m) / 1000
System with static head
H_sys = H_static + k × Q²
Minimum speed ratio
r_min = √(H_static / H_shut-off)

For unit conversions between m³/h, gpm, metres, feet, kW and hp, use the unit converter.