Fan power: airflow, pressure and motor size
How to work out fan power from airflow and pressure, apply the fan laws for speed and air density, and choose a motor size, with a worked example from 18,000 m³/h to an 11 kW motor.
Fans move air for ventilation, combustion, drying, cooling and dust extraction, and in most plants they run for thousands of hours a year. That makes the motor size and the running cost worth getting right. A fan that is matched to a motor by guesswork either trips on start-up or wastes energy for years. The good news is that the calculation is short: fan power comes from just two numbers, the airflow and the pressure the fan has to develop, divided by an efficiency. This guide walks through the formula, the fan laws for speed and air density, and a worked example from airflow to a standard motor size. For background on fan types, see the Wikipedia article on centrifugal fans.
The two numbers that set fan power
Airflow (Q) is the volume of air the fan moves, in m³/s. Duct and equipment data often give it in m³/h (divide by 3,600) or in CFM (1 CFM = 0.000472 m³/s).
Fan pressure is the pressure rise the fan has to supply to push that airflow through the ducts, filters, coils, dampers and grilles of the system, in pascals (Pa). It comes in two parts:
- Static pressure (p_s): the part that overcomes friction and the resistance of components.
- Velocity pressure (p_v): the kinetic energy of the moving air, p_v = ½ × ρ × v², where ρ is the air density in kg/m³ and v the air velocity in m/s. At 10 m/s in standard air (1.2 kg/m³), p_v = 0.5 × 1.2 × 10² = 60 Pa.
- Total pressure (p_t) = p_s + p_v.
Fan catalogues quote either total or static pressure, and a matching total or static efficiency. Always use the pair that belongs together: total pressure with total efficiency, or static pressure with static efficiency. Mixing them gives the wrong power.
The fan power formula
Air power
The useful power delivered to the air is simply flow times pressure:
P_air = Q × p_t (W, with Q in m³/s and p_t in Pa)
Shaft power
The fan wheel is not perfectly efficient, so the power needed at the fan shaft is larger:
P_shaft = Q × p_t / η_fan
Total efficiencies for industrial fans typically range from around 50% for small or simple designs to over 80% for large backward-curved and aerofoil fans running at their best point. Use the efficiency from the manufacturer's curve at your duty point whenever you have it.
Motor output and electrical input
A belt drive loses a few percent between motor and fan (roughly 3–5% for a well-tensioned V-belt drive), and a direct drive loses practically nothing:
P_motor = P_shaft / η_drive
Choose the next standard motor rating above P_motor. The electrical power drawn from the supply is the motor output divided by the motor efficiency: P_input = P_motor / η_motor.
Imperial units
If your data are in CFM and inches of water gauge, the familiar form is bhp = CFM × in. w.g. / (6356 × η_fan), which gives brake horsepower at the fan shaft (1 hp = 0.7457 kW). The engineering unit converter handles m³/h, CFM, Pa, in. w.g., kW and hp if your sources mix units.
Worked example: a ventilation supply fan
A belt-driven centrifugal fan must deliver 18,000 m³/h against a total pressure of 1,200 Pa in air at 20 °C. The fan curve gives a total efficiency of 72% at this point, and the belt drive is taken as 95% efficient.
- Airflow: Q = 18,000 / 3,600 = 5.0 m³/s
- Air power: P_air = 5.0 × 1,200 = 6,000 W = 6.00 kW
- Shaft power: P_shaft = 6.00 / 0.72 = 8.33 kW
- Motor output: P_motor = 8.33 / 0.95 = 8.77 kW
- Standard motor: the next IEC rating above 8.77 kW is 11 kW (7.5 kW is too small).
- Electrical input: with a motor efficiency of about 91%, typical for a modern 11 kW four-pole motor, P_input = 8.77 / 0.91 ≈ 9.6 kW. Over 6,000 running hours a year that is about 58,000 kWh.
Cross-check in imperial units: 5.0 m³/s = 10,594 CFM and 1,200 Pa = 4.82 in. w.g., so bhp = 10,594 × 4.82 / (6356 × 0.72) ≈ 11.2 hp ≈ 8.3 kW, the same shaft power. To size the drive itself, use the motor and gearbox selection calculator; for the belt and pulleys between motor and fan, see the V-belt drive guide.
The fan laws: changing speed
For a given fan running in the same system, flow, pressure and power change with speed (n) in a fixed pattern, known as the fan laws or affinity laws:
- Flow: Q₂ / Q₁ = n₂ / n₁
- Pressure: p₂ / p₁ = (n₂ / n₁)²
- Power: P₂ / P₁ = (n₂ / n₁)³
In the example, slowing the fan to 80% speed (for instance with a variable-frequency drive) gives 80% of the flow (4.0 m³/s), 64% of the pressure (768 Pa) and only 51% of the shaft power: 0.8³ × 8.33 = 4.27 kW. This cube law is why speed control saves so much energy on fans compared with throttling the air with a damper. The same laws apply to centrifugal pumps; the pump head and power calculator works the liquid side of the same idea.
The laws assume the system resistance rises with the square of the flow and that the fan efficiency stays roughly constant. They are a good estimate over a moderate speed range, but they do not hold where the system has a fixed pressure to overcome regardless of flow, or far from the fan's design point.
Hot air and density
A fan moves a fixed volume per revolution, so at the same speed its volume flow does not change with air density, but its pressure and power do, in direct proportion to density:
p₂ / p₁ = ρ₂ / ρ₁ and P₂ / P₁ = ρ₂ / ρ₁
Air density follows from the ideal gas law, ρ = p / (R × T), with R = 287 J/(kg·K) for dry air and T in kelvin. At sea level (101,325 Pa) that gives 1.204 kg/m³ at 20 °C and 0.834 kg/m³ at 150 °C, a ratio of 0.693.
If the example fan handled air at 150 °C at the same speed, it would develop 1,200 × 0.693 ≈ 831 Pa and need 8.33 × 0.693 ≈ 5.77 kW at the shaft. The reverse case catches people out: a fan selected to deliver 1,200 Pa in 150 °C gas needs about 8.33 kW hot, but when it starts on cold air at 20 °C the power rises to 8.33 / 0.693 ≈ 12.0 kW, more than an 11 kW motor can deliver. Hot-gas fans are therefore sized for the cold start, or started with the inlet damper closed or on a variable-speed drive. Altitude has the same effect as temperature: thinner air means less pressure and less power at the same speed.
Practical points for fan motor sizing
- Get the system pressure right first. Add up duct friction, fittings, filters (at their dirty, end-of-life pressure drop), coils, dampers and terminals; this is where most errors start.
- Read efficiency from the actual fan curve at the duty point, not a brochure maximum.
- Check the fan's power curve over its whole operating range. Forward-curved fans draw more power as flow rises, so a motor sized at the design point can overload if the system resistance turns out lower than calculated. Backward-curved fans have a non-overloading power curve with a peak near the design point.
- Allow for drive losses and pick the next standard motor size; do not round down.
- Size hot-gas fans for the coldest air they will ever start on, and account for altitude.
- Where the airflow varies, a variable-frequency drive usually pays for itself through the cube law.