Working out boiler duty and fuel from the steam you need
How the Steam & boiler duty calculator turns a steam demand into heat duty, boiler horsepower, equivalent evaporation and fuel burn, with a fully worked example and the limits to know.
Every boiler house starts with the same two questions: how much steam, at what pressure, does the plant need, and how much fuel will it take to make it? The Steam & boiler duty calculator answers both from five numbers, so you can check a supplier's quotation or plan a fuel store before anyone visits site.
How the calculation works
You enter steam required (kg/hour), steam pressure (barg, measured at the boiler), feedwater temperature (°C), boiler efficiency (%) and fuel calorific value (MJ/kg). The tool then works in this order:
- Absolute pressure = gauge pressure + 1.013 bar.
- Steam enthalpy = hf + hfg for saturated steam, interpolated from a built-in table that covers 1 to 30 bar absolute.
- Feedwater enthalpy = feedwater temperature × 4.186 kJ/kg.
- Heat duty (kW) = steam flow × (steam enthalpy − feedwater enthalpy) ÷ 3600.
- Boiler horsepower = duty ÷ 9.81, since 1 BHP is 9.81 kW.
- Equivalent evaporation = steam flow × (steam enthalpy − feedwater enthalpy) ÷ 2257, which is the "from and at 100 °C" basis boilers are compared on.
- Fuel (kg/hour) = duty × 3.6 ÷ (efficiency × calorific value).
Take the tool's default values: 2,000 kg/h of steam at 10 barg, feedwater at 80 °C, 82% efficiency and fuel at 42 MJ/kg (furnace oil).
Step | Calculation | Result |
|---|---|---|
Absolute pressure | 10 + 1.013 | 11.013 bar a |
Steam enthalpy (interpolated between 10 and 12 bar a) | 780.7 + 2000.3 | 2,781 kJ/kg |
Feedwater enthalpy | 80 × 4.186 | 334.9 kJ/kg |
Heat duty | 2000 × (2781.0 − 334.9) / 3600 | 1,359 kW |
Boiler horsepower | 1359 / 9.81 | 138.5 BHP |
Equivalent evaporation | 2000 × 2446.2 / 2257 | 2,168 kg/h |
Fuel consumption | 1359 × 3.6 / (0.82 × 42) | 142.1 kg/h |
Over a 24-hour day that is about 3,409 kg of fuel, and the steam-to-fuel ratio is 2000 ÷ 142.05 = 14.08 : 1. The tool also reports a saturation temperature of 184.0 °C and a latent heat of about 2,000 kJ/kg at this pressure.
Read the three results together. Heat duty in kW is what the burner must deliver to the water, boiler horsepower is a rating you can match against a nameplate, and fuel per hour is what the fuel store and the supplier contract must cover. If a quoted boiler is rated below the duty shown here, it will not carry the load at the entered pressure and feedwater temperature, however its brochure describes it. Change one input at a time to see its effect: raising feedwater from 80 °C to 105 °C removes 25 × 4.186 = 104.7 kJ/kg from the 2,446 kJ/kg the boiler must add, which is about 4% less duty and fuel.
What the tool assumes and leaves out
- Saturated steam only. Superheat adds enthalpy that a condensing load cannot use, so none is included.
- Pressure range of 1 to 30 bar absolute. Values outside the table are held at its ends.
- One efficiency figure that you supply. The tool gives a hint of about 80–85% on gas or oil and 65–72% on bagasse or husk, but it does not know your boiler.
- Your fuel value. Hints in the tool: furnace oil about 42, natural gas about 48, coal about 25, bagasse about 9.5 and rice husk about 13 MJ/kg. Use the figure from your own fuel analysis.
- No blowdown, no pipe losses, no start-up load. The daily figure assumes continuous running at the entered flow.
- No prices. It gives kilograms of fuel; multiply by your own fuel rate.
Common mistakes
- Entering the pressure at the point of use. The tool wants the pressure at the boiler, which is higher once line losses are counted.
- Typing absolute pressure as gauge. The tool adds 1.013 bar itself, so a gauge value is expected.
- Ignoring feedwater temperature. Cold make-up water needs far more heat than returned condensate; raising feedwater temperature cuts fuel.
- Mixing calorific units. The input is MJ/kg. A value in kcal/kg or kJ/kg will give nonsense.
- Comparing boilers by kg/h alone. Two boilers rated at the same kg/h can do different duty. Compare equivalent evaporation, or the duty in kW.
Try your own numbers in the Steam & boiler duty calculator. To estimate heat lost from a steam line or vessel wall, use the insulation thickness and heat loss calculator.