How a heat exchanger works
A plain-language guide to heat exchangers: how heat crosses the wall, the main types, why counter-current needs less area, and what fouling does over time.
A heat exchanger moves heat from a hotter fluid to a cooler one without letting the two mix. It is one of the most common items in a plant: it cools oil after a press, heats water for a process, condenses vapour from an evaporator and recovers heat that would otherwise be lost. The idea is simple, but the details decide whether one is the right size and keeps working for years.
The basic idea
Heat always flows from the hotter fluid to the colder one. In an exchanger the two fluids are kept apart by a metal wall, such as stainless steel, carbon steel, a copper alloy or titanium, and the heat crosses that wall. Three things set how much heat moves: the surface area of the wall, the temperature difference between the fluids, and an overall heat transfer coefficient, written U, that reflects how easily heat passes through the fluid films, the wall and any dirt on it.
The relation is Q = U × A × LMTD, where Q is the duty in watts, A the area in m² and LMTD the log mean temperature difference in kelvin. The same duty also equals the mass flow times the specific heat times the temperature change of either fluid, so the hot side and the cold side must balance.
Common types
- Shell and tube: a bundle of tubes inside a cylindrical shell, with one fluid in the tubes and the other around them. Robust, and widely used for higher pressures and temperatures.
- Plate: thin corrugated plates clamped in a frame, with the fluids in alternate gaps. Compact, with a high U, and easy to open for cleaning; the gaskets limit temperature and pressure.
- Double pipe: a pipe inside a pipe. Simple, and used for small duties.
- Air-cooled: finned tubes with fans blowing air across them, used where cooling water is scarce.
Counter-current and co-current
In counter-current flow the two fluids run in opposite directions; in co-current they run the same way. Counter-current keeps the temperature difference more even along the length, so the same duty needs less area, and the cold fluid can even leave hotter than the hot fluid leaves.
Take a duty of 250 kW, hot side 150 to 90 °C, cold side 30 to 80 °C and U = 800 W/m²K. Counter-current: the end differences are 70 K and 60 K, the LMTD is 64.9 K and the area is 250 × 1000 ÷ (800 × 64.9) = 4.8 m². Co-current: the end differences are 120 K and 10 K, the LMTD falls to 44.3 K and the area rises to 7.1 m², about 47% more surface for the same job. The cold flow in this example is about 4,300 kg/h of water, from 250 × 3600 ÷ (4.186 × 50).
Why performance drops over time
The commonest cause is fouling: scale, sludge, biological film or product deposits that build up on the surfaces and add resistance. U falls, outlet temperatures drift away from the design values and pressure drop rises. Designers add a fouling allowance, which is extra area, but it is used up as deposits grow.
Other causes are blocked or leaking tubes, air or other non-condensable gas trapped on the steam side, flow lower than design, and cooling water warmer than assumed. Hard water and sticky products foul faster, so the cleaning interval depends on the fluids, not on a fixed calendar.
Practical takeaways
- Start from the duty and the four temperatures, and check that the hot and cold sides balance.
- Prefer counter-current unless there is a reason not to.
- Ask the supplier which U and which fouling allowance they used.
- A very small temperature approach at one end makes the exchanger large, so check that you really need it.
- Check that gasket and tube materials suit your fluids, and that there is room to open and clean the unit.
- Follow the manufacturer's manual and your local pressure equipment rules.
To try your own temperatures and compare counter-current with co-current, use the Heat exchanger area calculator.