Heat exchanger area from duty and temperatures
How the Heat exchanger area calculator turns duty, four temperatures, flow arrangement and U into the log mean temperature difference and the surface area needed.
A heat exchanger that is too small never reaches its outlet temperatures; one that is too large wastes steel and money. The Heat exchanger area calculator takes the heat duty, the four terminal temperatures, the flow arrangement and an overall heat transfer coefficient, and gives the surface area needed with the log mean temperature difference (LMTD) shown.
How the calculation works
You enter duty (kW), hot side in and out (°C), cold side in and out (°C), the arrangement and U (W/m²K). The tool works out two end differences, called approaches:
- Counter-current: ΔT1 = hot in − cold out, and ΔT2 = hot out − cold in.
- Co-current: ΔT1 = hot in − cold in, and ΔT2 = hot out − cold out.
Then:
- LMTD (K) = (ΔT1 − ΔT2) ÷ ln(ΔT1 ÷ ΔT2). If the two differ by less than 0.01 K, the tool simply uses ΔT1.
- Area (m²) = duty × 1000 ÷ (U × LMTD).
- Flow check (kg/h) = duty × 3600 ÷ (4.186 × temperature change), worked for the hot and the cold side as if each were water.
The tool's starting values are a duty of 250 kW, hot side 150 to 90 °C, cold side 30 to 80 °C, counter-current, U = 800 W/m²K.
A worked example
- ΔT1 = 150 − 80 = 70 K and ΔT2 = 90 − 30 = 60 K.
- LMTD = (70 − 60) ÷ ln(70 ÷ 60) = 10 ÷ 0.1542 = 64.9 K.
- Area = 250 × 1000 ÷ (800 × 64.9) = 4.8 m².
- Hot flow = 250 × 3600 ÷ (4.186 × 60) = 3,583 kg/h, and cold flow = 250 × 3600 ÷ (4.186 × 50) = 4,300 kg/h.
Now run the same temperatures co-current. ΔT1 = 150 − 30 = 120 K and ΔT2 = 90 − 80 = 10 K, so LMTD = 110 ÷ ln(12) = 44.3 K and the area is 250 × 1000 ÷ (800 × 44.3) = 7.1 m². The same duty needs about 47% more surface, which is why counter-current is the default. The tool also warns that a close approach buys area steeply: halving the approach roughly doubles the exchanger.
Reading the result
The area is the clean, theoretical surface for the duty you entered. The two approaches show where the temperature margin is tight: a small figure at either end means a large exchanger that is sensitive to any error in the temperatures. In the example the approaches are 70 K and 60 K, close to each other, so the LMTD of 64.9 K is almost their simple average of 65 K. In the co-current case they are 120 K and 10 K, far apart, and the log mean falls to 44.3 K. The hot and cold side drops under Check let you confirm that the temperatures describe the duty you meant before you trust the area.
What the tool assumes and leaves out
- U is yours to enter. The tool only hints at ranges: plate water-water 3000–5000, shell and tube water-oil 300–600, steam-liquid 800–1500 W/m²K.
- Duty is an input. The tool does not calculate it from flows, and the flow check assumes water at 4.186 kJ/kg·K.
- If either end difference is zero or negative, the temperatures cross, no area can do the job, and the tool shows a dash instead of an area.
- There is no correction factor for multi-pass shell and tube units, and no fouling allowance, pressure drop, phase change or heat loss.
Common mistakes
- Entering a U taken from a different fluid pair or exchanger type.
- Swapping the cold in and cold out temperatures, which crosses the temperatures.
- Choosing co-current when the real unit runs counter-current.
- Treating the calculated area as the area to buy, with no margin for fouling.
- Entering a duty that does not match the temperature changes and flows actually available.
Try your own figures in the Heat exchanger area calculator. To size the line feeding it, use the pipe size and pressure drop calculator, and for the pump behind it the pump head and power calculator.